Powerware 9395 UPS 450–550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B102 UPS installation plan and unpackingUse the following basi
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B11ModelWeight kgShipping InstalledPowerware 9395-2*275 1610 1430
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B12Figure 2-1. UPS cabinet dimensions (front view)Figure 2-2.
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B13Figure 2-3. UPS cabinet dimensions (top view)Figure 2-4. UPS c
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B14Figure 2-5. UPS cabinet center of gravityFigure 2-6. Remote
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B15For external wiring requirements, including the minimum size o
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B16Terminals E1 through E12 are 2-hole bus bar mountings for s
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B17The line-to-line unbalanced output capability of the UPS is li
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B18Read and understand the following notes while planning and
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B192.3 Inspecting and unpacking the UPS cabinetThe UPS cabinet is
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONSThis manual contains important instructions that you should follow during installation and mainte
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B204. Remove the protective covering from the cabinet.5. R
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B213 UPS system installation3.1 Preliminary installation informat
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B22CAUTION•Donottiltcabinetsmorethan10°fromvertical.
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B23Figure 3-1. Removing left side shipping bracket
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B24Figure 3-2. Removing right side shipping bracket3.3 Battery
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B253.4 Installing UPS external and battery power wiringNOTE The U
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B26Figure 3-3. Conduit and wire entry locations
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B27Figure 3-4 a UPS power terminal locationsFigure 3-4. b UPS pow
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B28Figure 3-5 a, front view Figure 3-5 b, side view. UPS powe
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B293.4.2 Battery wiringCAUTIONWhen sizing the battery system, do
Powerware 9395 UPS 450–550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B Contents1 Introduction ...
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B30To install wiring to connections:1. Verify the UPS system
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B31Figure 3-7. Interface terminal locations
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B32Terminal TB1 Name Descrition1 Remote EPO NCDry contact used
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B33Figure 3-8. Interface terminal detail AANOTE All building alar
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B343.5.2 TB1 battery interface connectionsTo install wiring to
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B35NOTE Battery Aux and DC Shunt Trip wiring should be a minimum
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B36Figure 3-11. X-Slot communication bays3.6 Installing a remo
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B371. Securely mount the remote EPO switch. Recommended locatio
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B38Note Remote EPO switch rating is 24 Vdc, 1 A minimum.Note R
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B39Note Remote EPO switch rating is 24 Vdc, 1 A minimum.Note Remo
5.3 Operation ...
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B40Installation checklistr All packing materials and restrai
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B414 Understanding UPS operation4.1LookinginsidetheUPSsystem
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B424.2 ModesThe Powerware 9395 UPS supports a critical load in
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B43The inverter produces a three-phase AC output to a customer’s
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B44In bypass mode, the output of the system is provided with t
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B45During a utility power failure, the rectifier no longer has an
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B46NOTE If the load requires a neutral, a bypass source neutra
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B47NOTE If installing, as part of the UPS system, a maintenance b
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B485 UPS operating instructionsThis section describes how to o
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B495.1 UPS controls and indicatorsThe controls and indicators ide
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B51 IntroductionThe Eaton® Powerware® 9395 uninterruptible power
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B505.2 Using the control panelThe following paragraphs describ
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B515.2.2UsingtheLCDandpushbuttonsThe LCD on the control pane
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B525.2.3 Using the menuThe UPS menu bar allows you to display
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B53Function Subfunction OperationHistory Press the HISTORY pushbu
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B54Function Subfunction OperationkW Demand Log The kW Demand L
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B55Function Subfunction OperationMaximum Current LogThe Maximum C
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B56Function Subfunction OperationSystem Level 0 SetupFunction
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B57Function Subfunction OperationSet Date and Time DD/MM/YYYYThe
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B58Figure 5-6. System controls screen 25.2.7LoadoffscreenTh
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B596. On the System Controls screen, the power module (PM) stat
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B6Figure 1-1.Powerware 9395-550 (2*275) cabinet
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B605.3.3 Starting the power moduleTo start the power module witho
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B615.3.5 Transfer from bypass to normal modeTo transfer the cr
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B625.3.8 Charger controlTo turn the battery charger on or off, pe
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B635.3.10 Using the Remote Emergency Power-off switchA UPS eme
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B645.3.11 Using Mechanical Bypass SwitchThe operation of the inte
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B65Turn UPS from mechanical bypass to normal modeThe procedure
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B666 Responding to system events6.1 GeneralWhen the UPS system is
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B677 CommunicationThis chapter describes the communication fea
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B687.2PowerwareLanSafePowerManagementSoftwareEach Powerware
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B69MMDDYYYYHH:MM:SS.hhKYWDMESSAGE<CR><LF>Wh
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B71.1.2 Customer InterfaceBuilding Alarm Monitoring – Up to five i
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B707.4 Building alarm monitoringThis standard feature lets you co
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B718 UPS maintenanceThe components inside the UPS cabinet are
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B728.2 Performing preventive maintenanceThe UPS system requires v
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B738.3 Installing batteriesNOTE There is no DC disconnect devi
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B7410 Product specifications10.1 Model numbersThe UPS systems are
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B7510.2.3 EnvironmentalOperating Temperature0 to 40°C without
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide 1027574 Revision B81.3 Basic system configurationsThe following basic UPS system
UPS 450 - 550 kVA (2x225 - 2x275 kVA) User’s and Installation Guide1027574 Revision B91.6 Symbols, controls, and indicatorsThe following are examples