Page 1 - 0800-2000 - 0800-7500

USER MANUALFERRUPS0800-2000 - 0800-7500

Page 2 - User Manual

400 Using the FERRUPS’ Front Panel LightsThe FERRUPS display includes three lights that show you the status of FERRUPS operation.The red Alarm light m

Page 3 - Best Power Offices

To scroll down through menus or menu items in the same level:Press the t button on the right side of the display.To scroll up through menus or menu it

Page 4 - 100 Introduction

111 Enter password3 System StatusInfo5 System ConfigEnter password3 1 Unit Time3 2 Unit Date3 3 Unit Year3 4 AC Input Volts3 5 AC Output Volts3 6 AC I

Page 5 - 200 UPS Features

12503 Entering a PasswordBefore you can change the setting of some FERRUPS parameters or menu items, you must enter a password. Todo this, follow the

Page 6 - 300 Starting the UPS

3. Move the cursor to the first digit you want to change, and use the s and t buttons to increase or decrease thenumber. Repeat this step for each dig

Page 7 - Line (AC Input)

14Menu 2: System Status (continued)Menu 3: System Status InfoBy pressing ¿ while displaying this parameter, you can start a UserTest alarm to make sur

Page 8

15Menu 3: System Status Info (continued)Menu 4: System IDItem and SampleDisplayPassword toChangeRange Explanation3 10% Full Loadpctfload 90 %No chang

Page 9

16506 Reading the FERRUPS LogsYour FERRUPS makes an entry in its logs every time it sounds an alarm or runs on inverter (batterypower). This informati

Page 10 - 500 Using the Display

These are the inverter codes:Alarm LogThe Alarm Log is in menu 6, submenu 3.If you have already displayed inverter log entries, press the bottom right

Page 11 - Enter A Parameter

18Alarm Message MorseCodeWhat It Means How to ReactA Low Batteryvbatt 40.0 Vlowbatv 41.0 Vminbattv 38.34• —(A)The UPS has shut down because the batter

Page 12 - 5 2 7 VLLo

FERRUPS®User Manual0800-2000 through 0800-75002 kVA-7.5 kVA 50 and 60 HzUninterruptible Power SystemsIMPORTANT SAFETY INSTRUCTIONS.SAVE THESE INSTRUCT

Page 13 - 503 Entering a Password

19Alarm Message MorseCodeWhat It Means How to ReactK Circuit BreakerWarning Shutdown— • —(K)Your equipment is drawing more current(amps) than the UPS

Page 14 - 505 Parameters

20Optional Interface Kits: For computer systems that already have UPS monitoring software, BestPower offers interface cable kits for connecting the FE

Page 15 - Show Alarm Code #2

211. a. Press the bottom right button (below “Menu” on the display) to switch from the normal display tothe menus. The display will show the top menu,

Page 16 - Menu 4: System ID

22900 Specifications* Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are

Page 17 - 506 Reading the FERRUPS Logs

23AC Output with Nominal Input Power and Loads (Protected Equipment)Voltage Regulation: ±3% load regulation. Total voltage regulation under any line,

Page 18 - 600 Alarms

24ProtectionDC Input: DC fuse and battery charger overvoltage limit network.Output Protection: The ferroresonant transformer inherently limits current

Page 19

25incompatible or defective. Replacement or repair will be made at BEST POWER’s Worldwide Service,Highway 80, Necedah, Wisconsin 54646, U.S.A. Such re

Page 20 - 700 Communication

26This warranty does not include any taxes which may be due in connection with replacement or repair norany installation, transportation or postage co

Page 21 - 702 DB9 Port Pin Functions

271100 Notices2-3 kVA Soft-wired (Plug-in) and 50 Hz Models:This device complies with part 15 of the FCC rules. Operation is subject to the following

Page 22 - 800 Maintenance and Service

2Best Power OfficesBest PowerP.O. Box 280Necedah, WI 54646 U.S.A.Telephone: 1-608-565-7200Toll-Free: 1-800-356-5794 (U.S.A. and Canada)FAX: 1-608-565-

Page 23 - 900 Specifications

3Contents100 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 24 - Environment

4200 UPS FeaturesThe drawings below will help you identify the features on your UPS and separate battery cabinets.Back Panel of Standard Units* Back P

Page 25 - 1000 Warranty

5300 Starting the UPSNote: If you plan to store your UPS, the storage temperature must be between –20° and +40° Celsius (–4° and+104° Fahrenheit). If

Page 26

63Models with permanently attached power cords (shown):Plug in the UPS. If the plug on the UPS’ power cord does notmatch your outlet (receptacle), an

Page 27

7If your UPS has output receptacles/outlets on the back panel(shown) or on an attached internal bypass switch, plug theequipment you want to protect i

Page 28 - 1100 Notices

8b. Press the t button twice until the display shows “3 System Status Info.”c. Press ¿ once. The display will now show “31 Unit Time.” d. Press ¿. A